| Title: | Quadrilateral Distance Relay Based on Comparison of Samples. |
| Authors: | Verma, H. K. Rao, T. S. M. |
| Issue Date: | Jul-1977 |
| Publisher: | A paper recommended and approved by the IEEE Power System Relaying Committe of the IEEE Power Engineering Society for Presentation at the IEEE PES Summer Meeting, Mexio City, Mex., July 17-22, 1977. |
| Citation: | H. K. Verma, T. S. M. Rao, "Quadrilateral Distance Relay Based on Comparison of Samples. A paper recommended and approved by the IEEE Power System Relaying Committe of the IEEE Power Engineering Society for Presentation at the IEEE PES Summer Meeting, Mexio City, Mex", July 17-22, 1977. |
| Abstract: | The paper describes a quadrilateral distance relay based on the comparison of instantaneous values of input signals for the measurement of impedance. The relay principle and the measuring scheme, incorporating dualcomparison, a transactor matched to the protected system and built - in d.c. supply circuits, are described. Operation of the relay under adverse conditions is analysed. Results of the laboratory tests conducted to ascertain the relay performance on steady - state and transient conditions are presented. The relay has the merits of requiring very simple input circuits and a flexibility of adjusting the constituent characteristics (reactance and ohm) independently and shows a satisfactory performance overall. |